Performance-based vs prescriptive concrete specifications comes down to two questions: who designs the mix, and what gets tested. A prescriptive specification dictates the recipe — minimum cement content, maximum w/cm, caps on fly ash or slag, aggregate grading — and the specifier owns the outcome. A performance-based specification states the properties the concrete must reach (for example f′c = 4,500 psi at 28 days, surface resistivity ≥ 21 kΩ·cm, drying shrinkage ≤ 0.04%), names the test method and acceptance criteria, and leaves proportioning to the producer. Specify performance wherever a reliable test exists; keep prescriptive limits only where the code still demands them.

The gap between the two is not academic. When NRMCA reviewed 102 real US project specifications, 85% capped SCM content, 73% imposed a maximum w/cm where no exposure class required one, and fewer than 5% assigned ACI 318 exposure classes at all. In lab trials, performance mixes met every requirement at 9–15% lower material cost, and a bridge-deck mix with 15% less binder passed the chloride test that the prescriptive mix failed. This guide gives you the code limits, test criteria, an f′cr calculator and a decision tool to write a specification you can defend.

Key takeaways
  • Prescriptive = recipe + specifier risk. Performance = measurable result + producer risk for concrete as delivered.
  • ACI 318-19 sets a maximum w/cm only for exposure classes F1–F3, S1–S3, W2 and C2. Anywhere else, a w/cm limit is a project choice, not a code requirement.
  • Most real specifications are hybrids. The danger is clauses that conflict — e.g., a high minimum cement content plus a tight shrinkage limit.
📑 Table of Contents
  1. Side-by-side comparison
  2. What prescriptive specs control (and where they backfire)
  3. What a performance spec must contain
  4. Who carries the risk
  5. US, Canadian, UK/EU and Australian standards
  6. ACI 318-19 durability limits
  7. Required average strength f′cr + calculator
  8. Field and lab evidence
  9. Decision tool: which spec type fits?
  10. How to write a performance spec
  11. Hybrid spec conflicts to avoid
  12. Low-carbon concrete and performance specs
  13. Video explainers
  14. Free downloads and reference documents
  15. FAQ
  16. References

Performance-Based vs Prescriptive Concrete Specifications: Side-by-Side

PrescriptiveHybridPerformance
🧾 Recipe is specified
  • Min cement content, max w/cm, SCM caps, grading bands
  • Specifier owns whether it works
  • ASTM C94 Option B · BS 8500 prescribed · CSA prescription alternative
⚖️ Most real projects
  • Code durability limits plus some test criteria
  • Risk split must be written down explicitly
  • Highest risk of conflicting clauses
🎯 Result is specified
  • f′c, resistivity, shrinkage, air, ASR, GWP limits
  • Producer owns concrete as delivered
  • ASTM C94 Option A · BS 8500 designed/designated · CSA performance alternative
Moving right = more producer freedom, more producer responsibility, more prequalification testing
AspectPrescriptive specificationPerformance-based specification
What is specifiedIngredients and limits: min cementitious content, max w/cm, SCM type and percentage, aggregate grading, sometimes admixture brandsMeasurable fresh and hardened properties, each with a test method, test age and acceptance criterion
Who proportions the mixSpecifier (producer works inside tight limits)Producer, with contractor input on placeability and finishing
Who owns performance riskOwner/specifier — the producer only proves it followed the recipeProducer for concrete as delivered; contractor for placing, consolidation and curing
Acceptance basisBatch tickets plus strength cylindersPrequalification data plus acceptance tests at stated ages
Innovation (Type IL cement, ternary blends, recycled aggregate)Often blocked by caps and bansAllowed if the test criteria are met
Cost and carbonBinder-heavy; Colorado DOT found mixes running 500–1,000 psi above required strengthOptimized paste; NRMCA lab mixes cost 9–15% less in materials
Best fitSmall or site-batched work, properties with no reliable test, unknown supply chainLarge pours, durability-critical or low-carbon projects, certified producers with test records

What a Prescriptive Concrete Spec Controls — and Where It Backfires

Concrete mix constituents pie chart showing coarse aggregate, fine aggregate, cement, water and admixture — the proportions a prescriptive concrete specification fixes
A prescriptive spec fixes these proportions directly. A performance spec fixes what the hardened concrete must achieve.

Prescriptive clauses usually exist for a reason someone once had — a cracked slab, a slow-setting fly ash mix, a supplier who couldn't be trusted. The problem is that they outlive the reason. NRMCA's survey of producers ranked 15 common prescriptive requirements by how much they restrict optimization, then checked how often the top five appear in practice.

Prescriptive clauseWhy it gets writtenWhat the codes actually requirePerformance alternative
Max w/cm on interior members"Lower w/cm = more durable"ACI 318-19 sets w/cm only for F1–F3, S1–S3, W2, C2Specify f′c only; add a permeability test if durability matters
Minimum cement content ("6-sack mix")Legacy mix tables written before water reducers were commonACI 318 has no minimum cement content; ACI 301 floor minimums allow a test-slab alternativeStrength + drying shrinkage (ASTM C157) + finishability trial
Cap or ban on fly ash / slagFear of slow set and late finishingACI 318 limits SCM content only for exposure class F3Setting time (ASTM C403) + strength at a stated age
8–18 combined grading bandSegregation and finishability worriesNo ACI requirementWorkability and finishing performance; NRMCA tests found no significant benefit from the band
Ban on ASTM C595 / C1157 cementsUnfamiliarityBoth are recognized cement specificationsAccept with the same strength and durability tests
Note
ASTM C94 still offers Option C: the producer proportions the mix, but the purchaser sets a minimum cement content plus a minimum strength. An ASTM work item (WK91117) proposes deleting Option C because minimum cement contents block embodied-carbon targets without assuring performance.

What a Performance-Based Concrete Spec Must Contain

ACI 329R-14 frames every performance requirement in three parts. Miss one and the clause is unenforceable.

1PropertyWhat the concrete must do: strength, resistance to chloride ingress, low shrinkage, freeze-thaw resistance
2Test methodStandard procedure, specimen size, curing and test age (28 vs 56 days matters for SCM mixes)
3Acceptance criterionNumeric limit, number of tests, and what happens on a failure
Performance propertyTest methodExample acceptance criterionWhere it earns its place
Compressive strengthASTM C39 / AASHTO T 22ACI 318-19 26.12.3: every average of 3 consecutive tests ≥ f′c; no single test below f′c − 500 psi (f′c ≤ 5,000 psi) or 0.90f′cAll structural concrete; allow 56-day age for high-SCM mixes
Chloride penetrability (charge passed)ASTM C1202e.g., ≤ 1,500 coulombs at 45 days (used in a DOT HPC deck spec)Decks, parking structures, marine elements
Surface resistivityAASHTO T 358e.g., ≥ 21 kΩ·cm on 4×8 in. cylinders ("low" penetrability)Fast QC on the same cylinders as strength
Formation factorAASHTO R 101 (formerly PP 84)Limit set by freeze-thaw exposurePavements under the PEM approach
Drying shrinkageASTM C157 / AASHTO T 160e.g., ≤ 0.04% after 28 days of drying following 7 days moist curingSlabs on ground, decks, toppings
Restrained shrinkageAASHTO T 334 (ring test)Minimum time to crackingBridge decks, crack-sensitive elements
Freeze-thaw resistanceASTM C231 / C173 air content; Super Air Meter; ASTM C666Air content per ACI 318 Table 19.3.3.1F1–F3 exposures, pavements
Alkali-silica reactionAASHTO R 80 / ASTM C1778Prevention level matched to aggregate reactivityReactive aggregate regions
Sulfate resistanceASTM C1012Mortar-bar expansion limit for the binderS1–S3 exposures with alternative binders
Setting timeASTM C403Initial set within a window that suits the finishing crewFloors, hot or cold weather
Embodied carbonProduct-specific Type III EPDGWP limit (kg CO₂e/m³) per strength classLow-carbon and LEED projects

Chloride penetrability classes: ASTM C1202 and AASHTO T 358

Penetrability classASTM C1202 charge (coulombs)T 358 resistivity, 4×8 in. cylinder (kΩ·cm)T 358 resistivity, 6×12 in. cylinder (kΩ·cm)
High> 4,000< 12< 9.5
Moderate2,000–4,00012–219.5–16.5
Low1,000–2,00021–3716.5–29
Very low100–1,00037–25429–199
Negligible< 100> 254> 199
Tip
Resistivity takes seconds on the same cylinders you already break for strength, so it makes a cheap acceptance test. Use ASTM C1202 or a diffusion test for prequalification, and resistivity for routine acceptance. Note that results at 28 days understate SCM mixes, so state the test age (56 or 91 days is common).

Who Carries the Risk: Owner, Contractor and Producer

Responsibility and authority should be congruent.
Karthik Obla and Colin Lobo, Concrete International, August 2015
PartyUnder a prescriptive specUnder a performance spec
Owner / design engineerOwns mix adequacy; must justify every limitAssigns exposure classes per member, picks tests, ages and acceptance criteria, reviews prequalification data
Concrete producerBatches the recipe; liable only for conformance to itDesigns and proportions the mix, runs QC, guarantees properties as delivered
ContractorPlaces and finishes; "mix or workmanship?" disputes are commonResponsible for in-place concrete: placing, consolidation, curing, protection
Testing agencySlump, air, temperature, strength cylindersAdds prequalification and acceptance tests (resistivity, shrinkage, etc.)

ASTM C94 ordering options

ASTM C94 optionWho selects proportionsWhat the purchaser specifiesCharacter
Option AProducer, with full responsibilityStrength (default 28 days) plus other properties the purchaser needsPerformance
Option BPurchaserThe mixture proportions themselvesPrescriptive
Option CProducerMinimum cement content plus minimum strengthHybrid
Info
Canada's lesson: CSA A23.1 Table 5 offers only two alternatives, performance or prescription. Under the performance alternative, the supplier is responsible for the concrete as delivered and the contractor for the concrete in place. As Doug Hooton has explained in ACI presentations, an owner who adds prescriptive requirements turns the spec into a prescriptive one and takes the performance risk back. That is a big reason most Canadian specifications are now performance-based.

How US, Canadian, UK/EU and Australian Standards Handle It

RegionGoverning documentsPrescriptive routePerformance routeWorth knowing
🇺🇸 USAACI 318-19, ACI 301-20, ASTM C94ASTM C94 Option B; ACI 318 exposure-class w/cm limitsASTM C94 Option A; f′cr from producer test records (ACI 301)ACI 318 Section 1.10 allows approved alternatives; ACI 329R-14 shows how to write performance criteria
🇨🇦 CanadaCSA A23.1:24 / A23.2Prescription alternative — owner owns performancePerformance alternative — supplier (as delivered) and contractor (in place)The 2004 edition removed the old "common" middle option
🇬🇧 UKBS 8500-1:2023 with BS EN 206Prescribed concrete; standardized prescribed ST1–ST5 for small sites (mixers under 150 L)Designated (GEN, FND, PAV, RC — accredited producers only), designed, proprietaryST5 may be taken as no higher than C20/25 in design
🇪🇺 EuropeEN 206Prescribed; standardized prescribedDesigned concrete (specifier states properties; producer meets them)National annexes set durability limits
🇦🇺 AustraliaAS 1379-2007 with AS 3600Special class with composition limitsNormal class: N20–N50, slump 20–120 mm, 10/14/20 mm aggregate; special class with property limitsConcrete for AS 3600 exposure B2, C1, C2 or U is deemed special class

For a wider map of which standard governs which element, see our guide to Australian building design codes and the exposure-class approach in masonry durability design under AS 3700.

ACI 318-19 Durability Limits: The Prescriptive Floor You Can't Skip

ACI 318 still uses maximum w/cm plus minimum f′c for durability. Because w/cm cannot be reliably verified on site, the strength value becomes the acceptance proxy. The Licensed Design Professional can propose a performance alternative, such as a permeability test, under Code Section 1.10.

ClassExposureMax w/cmMin f′c, psi (MPa)Other requirements
F0No freeze-thawN/A2,500 (17)—
F1Freeze-thaw, limited water exposure0.553,500 (24)Air per Table 19.3.3.1
F2Freeze-thaw, frequent water exposure0.454,500 (31)Air per Table 19.3.3.1
F3Freeze-thaw, water + deicing chemicals0.40*5,000 (35)*Air; SCM limits per Table 26.4.2.2(b)
S1Moderate sulfate0.504,000 (28)Type II / MS cement
S2Severe sulfate0.454,500 (31)Type V / HS; no CaCl₂ admixture
S3Very severe sulfate0.45 (Opt. 1) / 0.40 (Opt. 2)4,500 / 5,000Opt. 1: Type V + pozzolan or slag
W0 / W1Dry, or wet without low-permeability needN/A2,500 (17)W1: alkali-aggregate provisions, 26.4.2.2(d)
W2In contact with water, low permeability required0.504,000 (28)Alkali-aggregate provisions, 26.4.2.2(d)
C0 / C1Dry, or moist without external chloridesN/A2,500 (17)Max chloride ion 1.00% / 0.30% (non-prestressed)
C2Moist + external chlorides (deicers, seawater)0.405,000 (35)Max chloride ion 0.15% (non-prestressed); 0.06% prestressed in all C classes

*F3 plain concrete: 0.45 and 4,500 psi. w/cm limits do not apply to lightweight concrete. Values from ACI 318-19 Table 19.3.2.1 as reproduced in NRMCA's exposure-class guide — check the current code edition before specifying.

Required Average Strength f′cr: Formulas and Calculator

Whatever the spec type, the producer proportions to f′cr, not f′c. The margin depends on how much test data the producer has, which is exactly where performance specs reward a well-run plant.

With a test record (≥ 15 consecutive tests, within 24 months, f′c within 1,000 psi)
f′c ≤ 5,000 psi:   f′cr = max { f′c + 1.34·k·s ,   f′c + 2.33·k·s − 500 }
f′c > 5,000 psi:   f′cr = max { f′c + 1.34·k·s ,   0.90·f′c + 2.33·k·s }
s = sample standard deviation · k = 1.16 (15 tests), 1.08 (20), 1.03 (25), 1.00 (30 or more); linear interpolation allowed. In SI the 500 psi term is 3.5 MPa and the 5,000 psi break is 35 MPa.
No usable test record
f′c < 3,000 psi → f′c + 1,000  |  3,000–5,000 psi → f′c + 1,200  |  > 5,000 psi → 1.10·f′c + 700
SI: < 21 MPa → f′c + 7.0 · 21–35 MPa → f′c + 8.3 · > 35 MPa → 1.10·f′c + 5.0
🧮 f′cr Calculator (ACI 301 / ACI 318 method)
Tip
Run the calculator with no record, then with s = 450 psi and 30 tests. For f′c = 4,500 psi the target falls from 5,700 psi to about 5,100 psi. That gap of roughly 600 psi is real cement your producer no longer has to add, and only a test-record-based (performance-friendly) spec captures it.

Field and Lab Evidence: What Actually Changes When You Switch

Lab study · Floor slabs
9–15%

Lower material cost for four performance mixes versus a prescriptive control (1,200 psi overdesign, max w/cm, 8–18 grading, no SCMs). All performance mixes met the strength, slump, shrinkage and set-time criteria. RMC Research Foundation / NRMCA, 2006

Lab study · HPC bridge deck
1,563 C

The DOT's prescriptive mix (705 lb/yd³ binder, w/cm 0.39, 15% fly ash + 7% silica fume) missed its own 1,500-coulomb limit at 45 days. All three performance mixes, at about 600 lb/yd³, passed with lower shrinkage. RMC Research Foundation / NRMCA, 2006

Colorado DOT · CDOT-2013-9
+500–1,000 psi

Minimum cement content controlled CDOT mix designs, so mixes overshot required strength by 500–1,000 psi. Suppliers on non-DOT work used less cement and more fly ash and still exceeded strength. University of Colorado Denver, 2013

Minnesota DOT · Bridge decks
2006 → 2009

Fully prescriptive deck mixes before 2006 cracked badly. MnDOT worked with ready-mix producers and had a performance-oriented spec by 2009, allowing SCM ranges and slump ranges, later adding lightweight aggregate and macrofibers. Deck performance improved. ACI University presentation

Cement, water and coarse aggregate — the mix constituents a producer can optimize under a performance-based concrete specification
Same constituents, different freedom: performance specs let the producer trade paste volume, SCM type and grading against measured results.
🗣️ The honest downsides (from people who have run these specs)
  • Lead time. STRUCTURE magazine (Lyons, 2025) warns that performance criteria ask for data a supplier may not have on hand, which can stretch submittal and placement schedules. Supplier sophistication also varies widely within a market.
  • Testing load and competence. A Hong Kong Development Bureau review (Prof. Y.L. Wong) lists intensive initial type testing and dependence on both designer and supplier competence as the main costs of performance specs.
  • Specs that never got updated. NRMCA found ACI 318 exposure classes assigned in fewer than 5% of specs reviewed, years after ACI 318-08 introduced them. Most "durability" clauses were copied, not engineered.

Decision Tool: Which Specification Type Fits Your Project?

🧭 Answer 7 questions
  1. Is there a standard test with an established limit for the property you care about (strength, chloride ingress, shrinkage, air)?
  2. Will local producers have recent test records (15+ tests, under 24 months) for similar mixes?
  3. Do candidate producers run certified QC and can they do prequalification testing?
  4. Does the schedule allow 5–8 weeks for prequalification (e.g., 7-day cure + 28-day shrinkage, 56-day resistivity)?
  5. Is the project targeting embodied carbon (GWP limits, EPDs, LEED)?
  6. Can the contract define acceptance testing and remedies for non-conforming concrete?
  7. Is this a small or site-batched job (a few cubic metres, hand or small mixer)?
Answer all seven questions to see a recommendation.

How to Write a Performance-Based Concrete Specification

How to Write a Performance-Based Concrete Specification⏱ 2 to 4 weeks of design-phase effort
  1. 1
    Assign exposure classes to every member
    List each concrete element (footings, slabs, walls, decks) and assign ACI 318 F, S, W and C classes, or the AS 3600 / BS 8500 equivalents. This decides where code limits apply and where you are free to specify performance.
  2. 2
    Choose properties that matter for each element
    Strength for everything; add chloride penetrability for C2, shrinkage for slabs and decks, air and freeze-thaw for F classes. Do not specify a property you will not test.
  3. 3
    Name the test method, specimen, curing and age
    Example: surface resistivity per AASHTO T 358 on 4×8 in. cylinders, moist cured, tested at 56 days. Use 56 or 91 days for high-SCM mixes.
  4. 4
    Set acceptance criteria and test frequency
    State the numeric limit, how many tests form a result, the sampling frequency, and the remedy (cores, in-place testing, price adjustment or removal) if a result fails.
  5. 5
    Define prequalification submittals
    Require trial-batch or field data that show each property before placement, plus strength test records (15+ tests within 24 months) to set f′cr.
  6. 6
    Delete conflicting prescriptive clauses
    Remove minimum cement contents, SCM caps and grading bands that are not code-required. Keep only the ACI 318 w/cm limits that apply to the assigned exposure classes.
  7. 7
    Hold a preconstruction meeting
    Agree mix submittals, placement and curing responsibilities, and the testing laboratory's scope with the contractor, producer and owner before the first pour.

Hybrid Specs: Clause Combinations That Make Mixes Impossible

NRMCA's P2P guidance accepts hybrid specifications, provided prescriptive and performance requirements for the same product do not conflict. These are the conflicts we see most often:

Conflicting combinationWhy it failsFix
High minimum cement content + tight drying-shrinkage limitMore paste means more shrinkage; the producer can't satisfy bothDrop the cement minimum and keep the shrinkage limit
Low SCM cap + aggressive GWP limitPortland cement drives most of concrete's CO₂Specify the GWP limit and remove the SCM cap
28-day acceptance on a 40–50% slag or fly-ash mixPenalizes slower-gaining, more durable bindersAccept strength and resistivity at 56 days
Prescriptive w/cm + "producer responsible for performance"Authority and responsibility sit with different partiesChoose who owns the mix design and write it down
Warning
If you are moving an existing spec to performance criteria, delete the old prescriptive clauses. Do not just add new tests on top. A spec that keeps both usually ends up with the cost of prescription and the testing burden of performance.

Low-Carbon Concrete: Why Performance Specs Matter More Every Year

About 90% of concrete's embodied emissions come from cement production (STRUCTURE magazine, 2025). Prescriptive minimum cement contents and SCM caps lock that carbon in. Performance specs open the routes that actually reduce it:

  • ✅ Portland-limestone cement (ASTM C595 Type IL) and performance-specified cement (ASTM C1157)
  • ✅ Higher slag, fly ash or calcined clay content, judged by strength and durability tests instead of percentage caps
  • ✅ Strength acceptance at 56 days where the structure is not loaded early
  • ✅ GWP limits per strength class backed by product-specific EPDs, which STRUCTURE magazine recommends, using NCSEA's performance-based concrete class table as a starting point

Pair this with an accurate structural demand. Over-specifying f′c on lightly loaded members is the other big carbon driver. Our flexural analysis and design of beams guide and RCC design spreadsheet help you check what strength the design actually needs.

Watch: Performance-Based Specifications Explained

The American Concrete Institute's state-of-the-industry session covers where performance specs stand today:

For a practitioner's view of the same debate, the Concrete Logic Podcast episode on performance vs prescriptive specifications is worth the listen:

Free Downloads and Reference Documents

DocumentPublisherFormatAccess
Guide to Specifying Concrete Performance (Phase II, Hover, Bickley, Hooton)NRMCA / RMC Research FoundationPDFFree download
Preparation of a Performance-Based Specification for Cast-in-Place Concrete (Phase I)RMC Research FoundationPDFFree download
Experimental Case Study Demonstrating Advantages of Performance Specifications (Obla, Lobo)RMC Research FoundationPDFFree download
Prescriptive Specifications: A Reality Check (Concrete International, Aug 2015)NRMCAPDFFree download
Guide to Selecting Exposure Classes (ACI 318-19 tables)NRMCAPDFFree download
TIP 2: Establishing the Required Average Strength f′crNRMCAPDFFree download
P2P Initiative resources and FAQNRMCAWebP2P hub · FAQ
ACI 329R-14 Report on Performance-Based Requirements for ConcreteAmerican Concrete InstitutePDF preview / purchaseFree preview
Developing Criteria for Performance-Based Concrete Specifications (CDOT-2013-9)Colorado DOTPDFFree download
Commentary on AASHTO R 101 (Performance Engineered Mixtures)CP Tech CenterWebRead online
Performance Engineered Concrete Paving Mixtures, TPF-5(368) reportsIowa DOT / FHWA pooled fundPDF setFree downloads
Performance Engineered Pavements technical briefFHWAPDFFree download
Surface resistivity / chloride penetration chartGilsonPDFFree download
A Scrutiny on Local Specification for Concrete (Prof. Y.L. Wong)Hong Kong Development BureauPDFFree download
Types of concrete specification (BS 8500 overview)Designing Buildings WikiWebRead online
AS 1379-2007 Specification and supply of concreteStandards AustraliaStandardBuy

Building a reference library? Our code-based civil engineering textbooks and handbooks list and free civil engineering books page collect the concrete technology titles behind these specs.

🏗️
Need a concrete specification reviewed or a structure designed?

M. Haseeb Mohal is a structural engineer working on reinforced concrete and steel design. For structural design support or a second look at a project's concrete requirements, see the portfolio or connect on LinkedIn.

FAQ: Performance-Based vs Prescriptive Concrete Specifications

What is the difference between a performance-based and a prescriptive concrete specification?
A prescriptive specification defines the mix: minimum cement content, maximum w/cm, SCM limits and aggregate grading. The specifier carries the risk that the recipe performs. A performance-based specification defines measurable results, such as compressive strength, chloride penetrability or drying shrinkage, with test methods and acceptance criteria. The producer designs the mix and is responsible for the concrete as delivered.
Does ACI 318 require a minimum cement content?
No. ACI 318 controls durability through maximum w/cm and minimum f′c for specific exposure classes (F1–F3, S1–S3, W2 and C2). It does not set a minimum cementitious content. ACI 301 does give minimum cementitious contents for floors, but it allows a test-slab alternative.
Who is responsible for concrete strength under a performance specification?
The concrete producer is responsible for the concrete meeting the specified properties as delivered. The contractor is responsible for placing, consolidating, curing and protecting it. CSA A23.1 Table 5 states this split explicitly. Under ASTM C94 Option A the producer takes full responsibility for selecting proportions.
What tests can replace a maximum w/cm limit for durability?
Common choices are ASTM C1202 charge passed, AASHTO T 358 surface resistivity, bulk resistivity or formation factor (AASHTO R 101), and chloride diffusion tests. ACI 318 still requires its w/cm limits for the listed exposure classes unless the building official approves an alternative under Section 1.10.
What are ASTM C94 Options A, B and C?
Option A: the producer selects the proportions and is responsible for the specified strength and other requirements. Option B: the purchaser takes responsibility for the mix proportions. Option C: the producer selects proportions, but the purchaser sets a minimum cement content and minimum strength. An ASTM work item proposes removing Option C.
How is required average strength f′cr calculated with no test records?
Under ACI 301/318: for f′c below 3,000 psi, f′cr = f′c + 1,000 psi; for 3,000 to 5,000 psi, f′c + 1,200 psi; above 5,000 psi, 1.10f′c + 700 psi. With at least 15 recent tests, the producer can use the lower statistical equations based on the standard deviation.
Can I mix performance and prescriptive requirements in one specification?
Yes. Most project specs are hybrids. Make sure the clauses cannot conflict (for example a high cement minimum and a tight shrinkage limit), and state clearly who owns the mix design. In Canada, adding prescriptive requirements to a CSA A23.1 performance specification shifts responsibility for performance back to the owner.

References

  1. ACI Committee 329 (2014). Report on Performance-Based Requirements for Concrete (ACI 329R-14). American Concrete Institute.
  2. ACI Committee 318 (2019). Building Code Requirements for Structural Concrete (ACI 318-19), Table 19.3.2.1 and Section 26.12.
  3. Obla, K.H. and Lobo, C.L. (2015). "Prescriptive Specifications: A Reality Check." Concrete International, August 2015, pp. 29–31.
  4. Obla, K. and Lobo, C. (2006). Experimental Case Study Demonstrating Advantages of Performance Specifications. RMC Research Foundation.
  5. Bickley, J., Hooton, R.D. and Hover, K.C. (2006). Preparation of a Performance-Based Specification for Cast-in-Place Concrete. RMC Research Foundation.
  6. Ballard, Z.J., Durham, S. and Liu, R. (2013). Developing Criteria for Performance-Based Concrete Specifications. Report CDOT-2013-9, Colorado DOT.
  7. Lyons, M. (2025). "Performance-Based Specifications and Embodied Carbon." STRUCTURE magazine.
  8. NRMCA. Guide to Selecting Exposure Classes and TIP 2: Establishing the Required Average Strength.
  9. ASTM C94/C94M, Standard Specification for Ready-Mixed Concrete; AASHTO T 358, Surface Resistivity Indication of Concrete's Ability to Resist Chloride Ion Penetration.
  10. CSA A23.1:24, BS 8500-1:2023, EN 206 and AS 1379-2007 (specification routes as summarized above).